CTC – EcoPart 414 – 400v (2xLEP) GSHP – 585700035

EcoPart 414 14kw Ground Source Heat Pump R407c – Three Phase – Fixed Speed

SKU: 7333077000554 Category:

Description

CTC’s EcoPart 400 range of ground source heat pumps offer an extremely efficient solution for space heating and hot water generation. Absorbing energy from the ground, boreholes or water the CTC EcoPart 400 raises the collected energy temperature by means of a refrigeration circuit providing higher temperatures to the heating system.

Thanks to a newly developed refrigeration circuit with an electronically controlled expansion valve and highly efficient compressor the EcoPart 400 boasts excellent efficiency with COP’s in excess of 5 (see data table). The compressor and refrigeration components are housed in a separate sound insulated unit. This provides exceptionally low noise levels (below 56dB(A)) making it one of the quietest heat pumps ever developed.

Connections for both brine and heating circuits at the rear, top and left and right sides of the heat pump offer the installer a highly flexible solution for new or existing installations.

The cooling module can be removed from the EcoPart 400 making maintenance of the refrigeration components much easier as well as aiding installation.

The CTC EcoPart 400 range of heat pumps has been developed over a 20 year period and is widely used in Northern Europe.

With a CTC EcoLogic controller or CTC EcoZenith intelligent thermal store the EcoPart can be integrated into a heating system with various heat inputs and numerous heat outputs. Alternatively using a CTC Basic Controller the EcoPart 400 can be controlled either on a fixed return temperature (also called fixed condensing) or thermostatic control.

Variation

Technical Information

Electrical Data EcoPart 406 EcoPart 408 EcoPart 410 EcoPart 412 EcoPart 414
Voltage 230V 1Ph
Rated Power kW 2.7 3.4 4.4 5.2 6.3
Rated Current A 14 19.5 21.6 27.1 33.2
Max. starting current A 30 30 30 30 30
IP Class IPX1
ErP data for heat pump
Energy class heating 35/55˚C (in package with control) A+++/A++ A+++/A++ A+++/A++ A+++/A++ A+++/A++
Energy class heating 35/55˚C (without control) A++/A++ A++/A++ A++/A++ A++/A++ A++/A++
Nominal heat output (Pdesignh) 35/55˚C kW 7/6 9/9 11/11 13/12 16/16
Operational data for heat pump
Output from compressor @ -5/45 kW 4.68 6.84 8.33 9.88 12.09
COP1) @ -5/45 3.09 3.34 3.3 3.3 3.24
Output from compressor kW 5.9 / 5.48 8.19 / 7.87 9.97 / 9.55 11.75 / 11.24 14.47 / 13.93
@ 0/35 / 0/45 / 0/55 / 5.17 / 7.55 / 9.28 / 10.97 / 13.40
COP @ 0/35 / 0/45 / 0/55 4.57 / 3.54 / 2.76 4.58 / 3.64 / 2.99 4.60 / 3.68 / 2.98 4.60 / 3.66 / 2.96 4.54 / 3.64 / 2.95
Output from compressor kW 6.81 / 6.49 9.44 / 9.05 11.42 / 10.99 13.53 / 12.95 16.48 / 15.98
@ 5/35 / 5/45 / 5/55 / 6.08 / 8.65 / 10.58 / 12.57 / 15.28
COP @ 5/35 / 5/45 / 5/55 5.24 / 4.15 / 3.18 5.02 / 4.04 / 3.30 5.20 / 4.16 / 3.28 5.11 / 4.11 / 3.35 5.13 / 4.11 / 3.28
Max. operating current of Compressor A 13 18.5 20.6 25 27.1
Sound effect according to EN12102 dB(A) 43 42.5 48.5 50.3 53
Heating System
Max. temperature heating medium (TS) °C 110
Heating medium system min. flow l/s 0.14 0.2 0.24 0.28 0.34
Heating medium system min. flow l/s 0.28 0.39 0.48 0.56 0.68
Brine System
Water volume (V) L 2.3 2.9 2.9 3.4 4.07
Brine system min/max temp (TS) ˚C -0.25
Brine system min/max pressure (PS) bar 0.2/3.0
Brine system min. flow Δt = 5°K l/s 0.27 0.31 0.38 0.44 0.53
Brine system nominal flow Δt = 3°K l/s 0.37 0.51 0.64 0.73 0.88
Other Data
Refrigerant quantity (R407C) kg 1.9 1.9 1.9 2.3 2.7
High pressure switch rating MPA/bar 3.3/31
Weight kg 138 143 148 164 164
Width x Height x Depth mm 600 x 760 x 672